← All standards & equipment
NACE/AMPP

NACE MR0103 / ISO 17945

Petroleum, petrochemical, and natural gas industries — Metallic materials resistant to sulfide stress cracking in corrosive petroleum refining environments

Issuing body
NACE/AMPP
Latest edition
2016
Region
USA, Global
Equipment items
2

Scope

Refining sour service — material requirements for SSC resistance in process units.

Key requirements (7)

  • Materials for sour refinery process service (downstream complement of ISO 15156).
  • Wet H2S service definition: water + H2S (any concentration in liquid water).
  • Carbon steel hardness limit: 200 HB (HV 215) max in HAZ and weld.
  • PWHT required for all welds in sour service.
  • Charpy impact: 27 J avg / 21 J single at MDMT.
  • Materials chemistry: Pcm ≤ 0.25, CE ≤ 0.43 typical for HIC resistance.
  • HIC-resistant plate testing per NACE TM0284 (CLR ≤ 15%, CTR ≤ 5%, CSR ≤ 2%).