Choose from Shell & Tube, Plate, Air Cooled, or Double Pipe
Set temperatures, flow rates, fluid types, and geometry
Get duty, area, U, NTU, pressure drop, and design recommendations
Download PDF report or share results via social media
Enter parameters and click Calculate
Calculating heat transfer coefficients…
Enter parameters and calculate
Calculating plate design…
Enter parameters and calculate
Calculating air cooler…
Enter parameters and click Calculate to generate the full engineering datasheet
Calculating fin-fan design…
Enter parameters and calculate
Calculating…
Enter temperatures and click Calculate
Answer the questions below to get a recommended heat exchanger type for your application.
Heat exchangers transfer thermal energy from a hot fluid to a cold fluid through a separating wall, without the fluids mixing. All designs are governed by the same three equations: the energy balance, the rate equation, and the design equation. Everything else is geometry and material science.
| Service | Shell & Tube | Plate HX | Air Cooler | Notes |
|---|---|---|---|---|
| Water – Water (clean) | 800–2 000 | 3 000–7 000 | — | Plate HX excels due to high turbulence |
| Steam condenser (shell) | 1 500–6 000 | 2 000–5 000 | — | Condensation is very high h; tube-side controls |
| Water – Light oil | 150–500 | 400–1 200 | — | Oil viscosity limits shell-side h |
| Water – Heavy oil / residue | 50–200 | Not recommended | — | High fouling, low h; S&T only |
| Gas – Liquid (high-P gas) | 100–350 | — | — | Gas side always limiting; fins help |
| Gas – Gas (no fins) | 15–60 | — | — | Both sides poor; use plate-fin for compact duty |
| Air cooling (process fluid) | — | — | 40–120 | Air h ≈ 30–80 W/m²K; fins increase effective area 10–20× |
| Reboiler / vaporiser | 500–2 500 | 1 000–4 000 | — | Nucleate boiling greatly enhances h |
| Crude oil train | 100–400 | — | — | Heavy fouling; design with 0.0005 m²K/W each side |
There are two equivalent design methods. LMTD is best when all four terminal temperatures are known (rating / checking an existing exchanger). NTU-ε is best when outlet temperatures are unknown (design from duty and inlet temperatures). Both methods must give the same answer.
The film coefficient h [W/m²·K] quantifies how effectively heat is conducted from the wall into the bulk fluid. It depends entirely on flow regime (Re), fluid properties (Pr), and geometry (D, L). This calculator uses the Gnielinski (1976) correlation for tube-side and the Bell-Delaware method for shell-side — both are the current industry standards.
| Correlation | Regime | Pr Range | Accuracy | Used by this calculator |
|---|---|---|---|---|
| Gnielinski (1976) | Turbulent + transition | 0.5–2 000 | ±10% | ✓ Default |
| Dittus-Boelter (1930) | Turbulent only (Re > 10 000) | 0.6–160 | ±25% | Not used |
| Sieder-Tate (1936) | Laminar, entry length dominated | 0.5–17 000 | ±20% | ✓ Laminar fallback |
| Petukhov-Kirillov | Turbulent Pr 0.5–2000 | 0.5–2 000 | ±12% | Not used (similar to Gnielinski) |
| Churchill-Bernstein | External crossflow cylinder | Any | ±20% | Shell side (idealised) |
Selecting the wrong exchanger type is one of the most expensive engineering mistakes. The decision matrix below captures the key engineering and economic trade-offs. Use the 🎯 HX Selector tab for an interactive recommendation.
| Criterion | Shell & Tube | Plate HX | Air Cooled | Double Pipe |
|---|---|---|---|---|
| Max pressure | ★★★★★ | ★★☆☆☆ | ★★★★☆ | ★★★★★ |
| Max temperature | ★★★★★ | ★★☆☆☆ | ★★★★☆ | ★★★★★ |
| High fouling service | ★★★★★ | ★★☆☆☆ | ★★★☆☆ | ★★★☆☆ |
| Area efficiency (U) | ★★★☆☆ | ★★★★★ | ★★☆☆☆ | ★★★☆☆ |
| Close ΔT_approach | ★★★☆☆ | ★★★★★ | ★★☆☆☆ | ★★★★☆ |
| No cooling water needed | ★☆☆☆☆ | ★☆☆☆☆ | ★★★★★ | ★☆☆☆☆ |
| Capital cost per kW | ★★★☆☆ | ★★★★☆ | ★★★☆☆ | ★★☆☆☆ |
| Ease of cleaning | ★★★☆☆ | ★★★★★ | ★★★☆☆ | ★★★★★ |
Fouling — the accumulation of unwanted deposits on heat transfer surfaces — is responsible for an estimated $7–10 billion per year in additional energy costs and maintenance in the process industries alone. Understanding its mechanisms and how to quantify its effect is essential for any serious design.
Pressure drop represents pumping energy consumed continuously over the exchanger's 20–30 year life. It must be constrained within allowable limits set by the pumping system, and it is in direct tension with heat transfer — the same geometric changes that improve h also increase ΔP.
TEMA (Tubular Exchanger Manufacturers Association) standards govern the mechanical design, fabrication tolerances, and materials for shell-and-tube heat exchangers. Understanding the 3-letter TEMA designation tells you the complete mechanical configuration at a glance.
This is the systematic procedure for designing a shell-and-tube heat exchanger from a process specification. Follow this sequence to avoid iteration traps and ensure every decision is technically defensible. For other types the logic is the same — only the correlation choices differ.
| Symbol | Quantity | SI Unit | Typical Values / Notes |
|---|---|---|---|
| Q | Heat duty | kW | Q = ṁ·c_p·ΔT — always balance hot and cold side first |
| U | Overall heat transfer coeff. | W/m²·K | 50–6 000 depending on service — see Section 1 table |
| A | Heat transfer area | m² | Typically based on tube outer surface (A_o = π·OD·N·L) |
| ΔT_lm | Log mean temperature difference | K (or °C) | Effective temperature driving force; always > 0 |
| F | LMTD correction factor | — | 0.75–1.0; <0.75 = problem; = 1.0 for pure counter-current |
| h | Film heat transfer coefficient | W/m²·K | 100–20 000 depending on fluid and velocity |
| R_f | Fouling resistance | m²·K/W | Typical: 0.0001–0.0009; from TEMA 9th ed. Table RGP-T-2.4 |
| NTU | Number of Transfer Units | — | NTU = U·A/C_min; typical 0.5–4.0 |
| ε | Heat exchanger effectiveness | — | 0–1; target 0.65–0.85 for most process exchangers |
| C_r | Heat capacity ratio C_min/C_max | — | 0 = condenser/evaporator; 1 = balanced; impacts ε−NTU curves |
| Re | Reynolds number | — | <2300 laminar; >10000 turbulent; keep >10000 in tubes |
| Pr | Prandtl number | — | Water: 2–7; oils: 30–1000; gases: 0.7; liquid metals: <0.05 |
| Nu | Nusselt number | — | Nu = h·D/k; links h to fluid properties and geometry |
| ΔP | Pressure drop | kPa (or bar) | Tube: 35–70 kPa; shell: 35–100 kPa; condensers: <15 kPa |
| LMTD | Log Mean Temperature Difference | K | LMTD_counter > LMTD_cross > LMTD_parallel always |
Enter vessel parameters and calculate per ASME VIII or EN 13445
| Material | Code | S @ 200°C (MPa) | S @ 300°C (MPa) | Notes |
|---|---|---|---|---|
| SA-516-70 / P265GH | ASME/EN | 138 | 127 | Most common vessel steel |
| SA-516-60 / P245GH | ASME/EN | 118 | 109 | Lower strength grade |
| SA-240-304 / 1.4301 | ASME/EN | 103 | 94 | Austenitic SS, corrosion resistance |
| SA-240-316L / 1.4404 | ASME/EN | 96 | 88 | SS with Mo for chloride resistance |
| SA-240-317L / 1.4438 | ASME/EN | 100 | 92 | High Mo SS |
| SA-516-70 HT / P355GH | ASME/EN | 172 | 161 | Higher strength, heat treated |
| Titanium Gr.2 / 3.7035 | ASME/EN | 69 | 62 | Excellent corrosion resistance |
| Hastelloy C276 / 2.4819 | ASME/EN | 138 | 128 | High-alloy for severe service |
TEMA 9th Edition Table RGP-T-2.4. Combine shell-side + tube-side fouling resistances for total R_f. Higher fouling = lower U and larger required area.
| Service | R_f (m²K/W) |
|---|---|
| Sea water below 52°C | 0.000088 |
| Sea water above 52°C | 0.000176 |
| Treated cooling tower water | 0.000176 |
| City or well water (hard) | 0.000352 |
| River water (min) | 0.000352 |
| River water (avg) | 0.000528 |
| Boiler feed water (treated) | 0.000088 |
| Boiler feed water (untreated) | 0.000528 |
| Distilled water | 0.000088 |
| Brine (refrigeration) | 0.000352 |
| Service | R_f (m²K/W) |
|---|---|
| Fuel oil (clean) | 0.000528 |
| Fuel oil (very heavy) | 0.000880 |
| Crude oil (below 150°C) | 0.000352 |
| Crude oil (150–230°C) | 0.000528 |
| Crude oil (above 230°C) | 0.000704 |
| Gasoline/naphtha (clean) | 0.000176 |
| Light hydrocarbons (clean) | 0.000176 |
| Light HC (with impurities) | 0.000352 |
| Refrigerants (liquid) | 0.000176 |
| Steam (oil-free) | 0.000088 |
| Service | R_f (m²K/W) |
|---|---|
| Amine solutions | 0.000176 |
| Caustic solutions (clean) | 0.000176 |
| Acid solutions (clean) | 0.000176 |
| Organic solvents (clean) | 0.000176 |
| Vegetable oils | 0.000528 |
| Boiler flue gas | 0.000880 |
| Engine exhaust gas | 0.001760 |
| Refrigerant vapour | 0.000176 |
| Compressed air (clean) | 0.000176 |
| Salt brines (process) | 0.000352 |
| Parameter | Shell & Tube | Plate HX | Air Cooled | Double Pipe |
|---|---|---|---|---|
| U (W/m²K) | 200–1000 | 1000–6000 | 30–80 | 300–1200 |
| Max Pressure | >600 bar | ~30 bar | ~100 bar | >300 bar |
| Max Temp (°C) | >600 | ~200 | >400 | >600 |
| Fouling Tolerance | Good | Low | Moderate | Good |
| Footprint | Large | Compact | Very Large | Small |
| Min Approach ΔT | 5–10°C | 1–2°C | 10–15°C | 5°C |
| Cleaning | Easy | Easy (gasketed) | Moderate | Easy |
| Typical Cost | $$ | $$$ | $$$ | $ |
| Best For | General service | Liquid-liquid | No cooling water | Small duties |
| Standards | TEMA / ASME VIII | ASME VIII | API 661 | TEMA / ASME |